Compact Substation Unit 12kV

  • Brand:
    Alaf Cekal

Description

11kV High Voltage Ring Main Unit            
(2 nos. Load Break Switch & 1 nos. of Fuse Switch)            
Rating                                           500kVA     1000kVA
Rated Voltage (kV)                                    12
Withstand Voltage at 50Hz (kVms)            28
Impulse Withstand Voltage (kV peak)        75
Frequency    (Hz) No. of Phase                50/3
Load Break Switch    (nos.)                         2
Rated Current of Load Break Switch (A)   630
Fuse Switch    (nos.)                                   1
Rated Current of Fuse Switch    (A)          200
Fuse Rating for Fuse Switch    (A)      50           100

Distribution Transformer            
Rating                                           500kVA     1000kVA
Transformer Ratio    (kV)                        11/0.433
Rated Tap Changing    (%)                   +2.5, +5.0
Withstand Voltage at 50Hz    (kVms)          28
Impulse Withstand Voltage    (kV peak)      75
Frequency    (Hz) No. of Phase                 50/3
Vector Group                                            Dyn11
Type of Cooling                                        ONAN
No load Losses    (kw)                      1.0             1.4
Load Losses at Full Load    (kw)       4.1             7.0

415 Low Voltage Switchboard – DIN Standard            
Rating                                           500kVA     1000kVA
Rated current    (A)                          800          1600
No. of Incoming Disconnector (A) 1x1000      2x1000
No. of Outgoing Fuseway    (A)      6x400      10x400
Frequency    (Hz) No. of Phase               50/3
Outgoing Fuse Rating    (A)                 250/NH2

Enclosure Dimension            
Rating                                           500kVA     1000kVA
Length x Width x Height (mm)        2600x2000x2000